Phase Angle Error CT PT Test Set

Brand Name : HNMC

Model Number : HEWE series

Place of Origin : China

MOQ : 1

Price : Negotiable

Payment Terms : L/C, T/T, Western Union

Supply Ability : 30 sets per month

Delivery Time : 30-45 days

Packaging Details : Wooden Package

Accuracy class : 2

Current Range1 : 1A, 5A

Voltage Range : 100V、100/√3V

Test Function : Ratio, Ratio error, phase angle error......

Percentage error : Less than 1.5%*FS

Display : big LCD

Contact Now

Digital Transformer Tester HEWE series CT PT Test Equipment Comparator

Technical Parameter

Accuracy class 2
Current range 5A, 1A
Voltage range 100V,100/√3V
Percentage Error Less than 1.5%*FS
Basic Error
When testing CT PT error & impedance & admittance, the error will not beyond:

ΔX=±(X*2%+Y*2%+Dx)

ΔY=±(X*2%+Y*2%+Dy)

ΔX: basic error limit value of in-phase component

ΔY: basic error limit value of Quadrature Component

X: Indication absolute value of in-phase component

Y: Indication absolute value of Quadrature Component

Dx & Dy: Zero error and Quantizing Error

When testing CT & PT, Dx,Dy=1(or 2)%*(Error limit value of CT & PT

When testing Z & Y, Dx,Dy= 3 digits

Measure Range & Resolution

CT PT class Test Range Resolution
In-phase component Quadrature Component In-phase component Quadrature Component
0.01 ±0.4000 ±13.752 0.0001% 0.001'
0.02
0.05
0.1 ±4.000 ±137.52 0.001% 0.01'
0.2
0.5
1.0 ±40.00 ±999.9 0.01% 0.1'
Impedance Measure Range & Resolution
Range Measure Range (Ω) Resolution
5A ±1.000 0.0001
1A ±6.000 0.0001
Admittance Measure Range & Resolution
Range Measure Range (mS) Resolution
100V ±9.9999 0.0001
57.7V ±9.9999 0.0001

Features

1) LCD display

2) Test of ratio, ratio error, phase angle error, impedance, admittance

3) Test data values are all displayed

4) Used for testing of class 1 to 0.01 instrument transformer with rated current 5A and 1A,

rated voltage 100V, 100V√3V

5) Display ratio error & phase angle error of all test points under rated burden or lower limit

burden 1%-120% Rated current or 20%-120% rated voltage

Phase Angle Error CT PT Test Set

Design for options


Product Tags:

1.5%FS CT PT Test Set

      

1.5%FS 100V CT PT Test Set

      

5A 1.5%FS ratio ct and pt testing

      
Quality Phase Angle Error CT PT Test Set for sale

Phase Angle Error CT PT Test Set Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Metrum Henan Electric Technology Co.,Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)